Skip Navigation

Administrative Rules Home Administrative Rules

DAR File No. 32409

This filing was published in the 03/15/2009, issue, Vol. 2009, No. 6, of the Utah State Bulletin.

Environmental Quality, Drinking Water

R309-530-6

Slow Sand Filtration

NOTICE OF PROPOSED RULE

DAR File No.: 32409
Filed: 02/26/2009, 10:30
Received by: NL

RULE ANALYSIS

Purpose of the rule or reason for the change:

The purpose of this amendment is to correct a mistake in the filtration rate for slow sand filtration.

Summary of the rule or change:

This amendment corrects a mistake in the filtration rate from 0.01 gpm/sf to 0.1 gpm/sf for slow sand filtration.

State statutory or constitutional authorization for this rule:

Section 19-4-104

Anticipated cost or savings to:

the state budget:

None--Since this amendment only corrects an error in the numerical value expressed in rule (the expression in brackets is incorrect), there is no cost to the state budget as a result of this proposed amendment.

local governments:

None--Since this amendment only corrects an error in the numerical value expressed in rule (the expression in brackets is incorrect), there is no cost to existing water systems owned by local government as a result of this proposed amendment.

small businesses and persons other than businesses:

None--Since this amendment only corrects an error in the numerical value expressed in rule (the expression in brackets is incorrect), there is no cost to small businesses such as consulting engineering companies as a result of this proposed amendment.

Compliance costs for affected persons:

None--Since this amendment only corrects an error in the numerical value expressed in rule (the expression in brackets is incorrect), there is no cost to consumers of water systems as a result of this proposed amendment.

Comments by the department head on the fiscal impact the rule may have on businesses:

The department agrees that the proposed change to this rule will have little to no detrimental impact on existing water systems or to new public water systems. William Sinclair, Acting Executive Director.

The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

Environmental Quality
Drinking Water
150 N 1950 W
SALT LAKE CITY UT 84116-3085

Direct questions regarding this rule to:

Bill Birkes at the above address, by phone at 801-536-4201, by FAX at 801-536-4211, or by Internet E-mail at bbirkes@utah.gov

Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

04/14/2009

This rule may become effective on:

04/21/2009

Authorized by:

Ken Bousfield, Director

RULE TEXT

R309. Environmental Quality, Drinking Water.

R309-530. Facility Design and Operation: Alternative Surface Water Treatment Methods.

R309-530-6. Slow Sand Filtration.

(1) Acceptability.

Slow sand filtration means a process involving passage of raw water through a bed of sand at low velocity resulting in substantial particle removal by physical and biological mechanisms. The acceptability of slow sand filters as a substitute for "conventional surface water treatment" facilities (detailed in R309-525) shall be determined by the Executive Secretary based on suitability of the source water and demand characteristics of the system.

(2) Source Water Quality.

The Executive Secretary may impose design requirements in addition to those listed herein, in allowing this process. The following shall be considered, among other factors, in determining whether slow sand filtration will be acceptable:

(a) Source water turbidity must be low and consistent. Slow Sand Filtration shall be utilized only when the source waters have turbidity less than 50 NTU and color less than 30 units (see R309-515-5(2)(a)).

(b) The nature of the turbidity particles shall be considered. Turbidity must not be attributable to colloidal clay.

(c) The nature and extent of algae growths in the raw water shall be considered. Algae must not be a species considered as filter and screen-clogging algae as indicated in "Standard Methods for the Examination of Water and Wastewater" prepared and published jointly by American Public Health Association, American Water Works Association, and Water Environment Federation. High concentrations of algae in the raw water can cause short filter runs; the amount of algae, expressed as the concentration of chlorophyll "a" in the raw water shall not exceed 0.005 mg/l.

(3) Pilot Plant Studies.

The Executive Secretary shall allow the use of Slow Sand Filtration only when the supplier's engineering studies show that the slow sand facility can consistently produce an effluent meeting the quality requirements of rule R309-200. The Executive Secretary should be consulted prior to the detailed design of a slow sand facility.

(4) Operation.

Effluent from a Slow Sand Filtration facility shall not be introduced into a public water supply until an active biological mat has been created on the filter.

(5) Design requirements.

The following design parameters shall apply to each Slow Sand Filtration plant:

(a) At least three filter units shall be provided. Where only three units are provided, any two shall be capable of meeting the plant's design capacity (normally the projected "peak daily flow") at the approved filtration rate. Where more than three filter units are provided, the filters shall be capable of meeting the plant design capacity at the approved filtration rate with any one filter removed from service.

(b) All filters shall be protected to prevent freezing. If covered by a structure, enough headroom shall exist to permit normal movement by operating personnel for scraping and sand removal operations. There shall be adequate manholes and access ports for the handling of sand. An overflow at the maximum filter water level shall be provided.

(c) The permissible rates of filtration shall be determined by the quality of the source water and shall be determined by experimental data derived during pilot studies conducted on the source water. Filtration rates of 0.03 gpm/sf to 0.1[0.01] gpm/sf shall be acceptable (equivalent to two to six million gallons per day per acre). Somewhat higher rates may be acceptable when demonstrated to the satisfaction of the Executive Secretary.

(d) Each filter unit shall be equipped with a main drain and an adequate number of lateral underdrains to collect the filtered water. The underdrains shall be so spaced that the maximum velocity of the water flow in the underdrain will not exceed 0.75 fps. The maximum spacing of the laterals shall not exceed three feet if pipe laterals are used.

(e) Filter sand shall be placed on graded gravel layers for an initial filter sand depth of 30 inches. A minimum of 24 inches of filter sand shall be present, even after scraping. The effective size of the filter sand shall be between 0.30 mm and 0.45 mm in diameter. The filter sand uniformity coefficient shall not exceed 2.5. Further, the sand shall throughly washed and found to be clean and free from foreign matter.

(f) A three-inch layer of well rounded sand shall be used as a supporting media for filter sand. It shall have an effective size of 0.8 mm to 2.0 mm in diameter and the uniformity coefficient shall not be greater than 1.7.

(g) A supporting gravel media shall be provided. It shall consist of hard, durable, rounded silica particles and shall not include flat or elongated particles. The coarsest gravel shall be 2.5 inches in size when the gravel rests directly on the strainer system, and must extend above the top of the perforated laterals. Not less than four layers of gravel shall be provided in accordance with the following size and depth distribution when used with perforated laterals:

 

TABLE 530-1


Size Depth
2 1/2 to 1 1/2 inches 5 to 8 inches
1 1/2 to 3/4 inches 3 to 5 inches
3/4 to 1/2 inches 3 to 5 inches
1/2 to 3/16 inches 2 to 3 inches
3/16 to 3/32 inches 2 to 3 inches

 

Reduction of gravel depths may be considered upon justification to the Executive Secretary when proprietary filter bottoms are specified.

(h) Slow sand filters shall be designed to provide a depth of at least three to five feet of water over the sand.

(i) Each filter shall be equipped with: a loss of head gauge; an orifice, venturi meter, or other suitable metering device installed on each filter to control the rate of filtration; and an effluent pipe designed to maintain the water level above the top of the filter sand.

(j) Disinfection of the effluent of Slow Sand Filtration plants will be required.

(k) A filter-to-waste provision shall be included.

(l) Electrical power shall be available at the plant site.

 

KEY: drinking water, direct filtration, slow sand filtration, membrane technology

Date of Enactment or Last Substantive Amendment: April, 2009[December 9, 2002]

Notice of Continuation: April 2, 2007

Authorizing, and Implemented or Interpreted Law: 19-4-104

 

 

ADDITIONAL INFORMATION

Text to be deleted is struck through and surrounded by brackets (e.g., [example]). Text to be added is underlined (e.g., example). Older browsers may not depict some or any of these attributes on the screen or when the document is printed.

For questions regarding the content or application of this rule, please contact Bill Birkes at the above address, by phone at 801-536-4201, by FAX at 801-536-4211, or by Internet E-mail at bbirkes@utah.gov

For questions about the rulemaking process, please contact the Division of Administrative Rules (801-538-3764). Please Note: The Division of Administrative Rules is NOT able to answer questions about the content or application of these administrative rules.

Last modified:  03/13/2009 3:46 PM