File No. 33881

This rule was published in the September 1, 2010, issue (Vol. 2010, No. 17) of the Utah State Bulletin.


Public Safety, Fire Marshal

Rule R710-3

Assisted Living Facilities

Notice of Proposed Rule

(Amendment)

DAR File No.: 33881
Filed: 08/03/2010 12:14:04 AM

RULE ANALYSIS

Purpose of the rule or reason for the change:

The purpose of the rule change is to update an incorporated reference. It is proposed to update the 2006 edition of the International Fire Code to the 2009 edition as enacted and amended by the Utah State Legislature in the State Fire Code Adoption Act. It is also proposed to eliminate the 2006 International Building Code as an incorporated reference since it is adopted by the Utah State Legislature in the Building Construction Standards Act.

Summary of the rule or change:

In Subsection R710-3-1(1.1), it is proposed to update the 2006 International Fire Code to the 2009 International Fire Code. In Subsection R710-3-1(1.2), it is proposed to delete the 2006 International Building Code due to its adoption in the Building Construction Standards Act. In Subsections R710-3-3(3.1.3) and (3.1.4), it is proposed to eliminate the installation of fire alarms in existing facilities unless required by NFPA 72, National Fire Alarm Code. There are other reference changes throughout the rule to make them consistent with the 2009 International Fire Code.

State statutory or constitutional authorization for this rule:

  • Section 53-7-204

This rule or change incorporates by reference the following material:

  • Updates International Fire Code, published by International Code Council, Inc., 03/01/2009
  • Removes International Building Code, published by International Code Council, Inc., 03/01/2006

Anticipated cost or savings to:

the state budget:

There would be an aggregate anticipated cost of approximately $1,000 to purchase the needed copies of the 2009 International Fire Code for state usage.

local governments:

The aggregate anticipated cost to local government would be approximately $68 per International Fire Code. There would be approximately 200 fire departments that would purchase a 2009 International Fire Code totaling approximately $14,000. Some might purchase more than one book but that number is unknown.

small businesses:

There would be no aggregate anticipated cost or savings to small businesses because small businesses rarely, if ever, purchase a regulatory code.

persons other than small businesses, businesses, or local governmental entities:

There would be no other persons affected by these proposed amendments. Those affected would be those in government that would use the code.

Compliance costs for affected persons:

The only compliance cost for affected persons would be the purchase of the newly adopted 2009 International Fire Code which would be by those in government that would be using the standard as a regulatory reference.

Comments by the department head on the fiscal impact the rule may have on businesses:

There is no fiscal impact on business for the implementation of these proposed rule changes. The only fiscal impact would be to government agencies to purchase the newly adopted 2009 International Fire Code.

D. Lance Davenport, Commissioner

The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

Public Safety
Fire Marshal
5272 S COLLEGE DR
MURRAY, UT 84123-2611

Direct questions regarding this rule to:

  • Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at [email protected]

Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

10/01/2010

This rule may become effective on:

10/08/2010

Authorized by:

Ron Morris, Utah State Fire Marshal

RULE TEXT

R710. Public Safety, Fire Marshal.

R710-3. Assisted Living Facilities.

R710-3-1. Introduction.

Pursuant to Title 53, Chapter 7, Section 204, of the Utah Code Annotated 1953, the Utah Fire Prevention Board adopts for the purpose of establishing minimum standards for prevention of fire and for the protection of life and property against fire and panic in assisted living facilities. The requirements listed in this rule text are in addition to the requirements listed in R710-9, Rules Pursuant to the Utah Fire Prevention Law.

There is adopted as part of these rules the following codes which are incorporated by reference:

1.1 International Fire Code (IFC), [2006]2009 edition, excluding appendices, as published by the International Code Council, Inc. (ICC), [except as amended by provisions listed in R710-3-3, et seq]and as enacted and amended by the Utah State Legislature in Sections 102 and 201 of the State Fire Code Adoption Act.

[1.2 International Building Code (IBC), 2006 edition, as published by the International Code Council, Inc. (ICC), and as adopted under the authority of the Uniform Building Standards Act, Title 58, Chapter 56, Section 4, Utah Code Annotated 1953 and the Utah Administrative Code, R156-56-701.

]1.[3]2 Copies of the above code are on file in the Office of Administrative Rules and the State Fire Marshal.

 

R710-3-3. Amendments and Additions.

3.1 General Requirements

3.1.1 All facilities shall be inspected annually and obtain a certificate of fire clearance signed by the AHJ.

3.1.2 All facility administrators shall develop emergency plans and preparedness as required in IFC, Chapter 4.

3.1.3 IFC, Chapter 9, Section[s] 907.3[.1.2 and 907.3.1.8 is deleted] Where required in existing buildings and structures, is deleted and rewritten as follows: "An approved automatic fire detection system shall be installed in accordance with the provisions of this code and NFPA 72. Devices, combinations of devices, appliances, and equipment shall be approved. The automatic fire detectors shall be smoke detectors, except an approved alternative type of detector shall be installed in spaces such as boiler rooms where, during normal operation, products of combustion are present in sufficient quantity to actuate a smoke detector".

3.1.4. IFC, Chapter 46, Section 4603.6.2 and 4603.6.7 are deleted and rewritten as follows: "An approved automatic fire detection system shall be installed in accordance with the provisions of this code and NFPA 72. Devices, combinations of devices, appliances, and equipment shall be approved. The automatic fire detectors shall be smoke detectors, except an approved alternative type of detector shall be installed in spaces such as boiler rooms where, during normal operation, products of combustion are present in sufficient quantity to actuate a smoke detector".

3.2 Type I Assisted Living Facilities

3.2.1 Type I Limited Capacity Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-3, and maintained in accordance with the IBC and IFC.

3.2.2 Type I Limited Capacity Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

3.2.3 Residents in Type I Limited Capacity Assisted Living Facilities shall be housed on the first story only, unless an approved outside exit leading to the ground level is provided from any upper or lower level. Split entry/split level type homes in which stairs to the lower and upper level are equal or nearly equal, may have residents housed on both levels when approved by the AHJ.

3.2.4 In Type I Limited Capacity Assisted Living Facilities, resident rooms on the ground level, shall have emergency escape or rescue windows as required in IFC, Chapter 10, Section [1025]1029.

3.2.5 In Type I Limited Capacity Assisted Living Facilities an approved independent smoke detector shall be installed and maintained by location as required in IFC, Chapter 9, Section 907.2.[10.1]11.2.

3.2.6 Type I Small Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-4, and maintained in accordance with the IBC and IFC.

3.2.7 Type I Small Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

3.2.8 Type I Large Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-1, and maintained in accordance with the IBC and IFC.

3.2.8.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

3.2.9 In a Type I Assisted Living Facility, non-ambulatory persons are permitted after receiving approval for a variance from the Utah Department of Health as allowed in Utah Administrative Code, R432-2-18.

3.3 Type II Assisted Living Facilities

3.3.1 Type II Limited Capacity Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-4, and maintained in accordance with the IBC and IFC.

3.3.2 Type II Limited Capacity Assisted Living Facilities shall have an approved automatic fire extinguishing system installed in compliance with the IBC and IFC, or provide a staff to a resident ratio of one to one on a 24 hour basis.

3.3.3 Type II Small Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-1, and maintained in accordance with the IBC and IFC.

3.3.3.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

3.3.4 Type II Small Assisted Living Facilities shall have a minimum corridor width of six feet.

3.3.4.1 Type II Small Assisted Living Facilities licensed before November 16, 2004, shall have a minimum corridor width of six feet or a path of egress that is acceptable to the AHJ.

3.3.5 Type II Large Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-2, and maintained in accordance with the IBC and IFC.

3.3.5.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

3.3.6 In Type II Assisted Living Facilities, where the clinical needs of the patients require specialized security, approved access controlled egress doors may be installed when all of the following are met:

3.3.6.1 The controlled egress doors shall unlock upon activation of the automatic fire sprinkler system or the automatic fire detection system.

3.3.6.2 The facility staff can unlock the controlled egress doors by either sensor or keypad.

3.3.6.3 The controlled egress doors shall unlock upon loss of power.

3.3.6.4 The secure area or unit with controlled egress doors shall be located at the level of exit discharge in Type V construction.

3.3.7 In Type II Assisted Living Facilities, where the clinical needs of the patients require approved, listed delayed egress locks, they shall be installed on doors as allowed in IBC, Section 1008.1.[8.6]9.7. Section 1008.1.[8.6]9.7(3) is deleted. The secure area or unit with delayed egress locks shall be located at the level of exit discharge in Type V construction.

3.3.8 In a Type II Assisted Living Facility, non-ambulatory persons are permitted after receiving approval for a variance from the Utah Department of Health as allowed in Utah Administrative Code, R432-2-18.

3.4 Residential Treatment/Support Assisted Living Facilities

3.4.1 Residential Treatment/Support Limited Capacity Assisted Living Facility shall be constructed in accordance with IBC, Residential Group R-3, and maintained in accordance with the IBC and IFC.

3.4.2 Residential Treatment/Support Limited Capacity Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

3.4.3 Residents in Residential Treatment/Support Limited Capacity Assisted Living Facilities shall be housed on the first story only, unless an approved outside exit leading to the ground level is provided from any upper or lower level. Split entry/split level type homes in which stairs to the lower and upper level are equal or nearly equal, may have residents housed on both levels when approved by the AHJ.

3.4.4 In Residential Treatment/Support Limited Capacity Assisted Living Facilities, resident rooms on the ground level, shall have emergency escape or rescue windows as required in I[B]FC, Chapter 10, Section [1026]1029.

3.4.5 In Residential Treatment/Support Limited Capacity Assisted Living Facilities an approved independent smoke detector shall be installed and maintained by location as required in IFC, Chapter 9, Section 907.2.[10.1]11.2.

3.4.6 Residential Treatment/Support Small Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-4, and maintained in accordance with the IBC and IFC.

3.4.6.1 IFC, Chapter 9, Section 903.2.[7]8 is amended to add the following: Exception: Residential Treatment/Support Assisted Living Facility classified as Group R-4, not more than 4500 gross square feet, and not containing more than 16 ambulatory, non-restrained residents, is allowed provided the building is equipped throughout with an approved fire alarm system that is interconnected and receives its primary power from the building wiring.

3.4.7 Residential Treatment/Support Small Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

3.4.8 Residential Treatment/Support Large Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-1, and maintained in accordance with the IBC and IFC.

3.4.8.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

3.4.9 In a Residential Treatment/Support Assisted Living Facility, residents with compromised ambulatory capacity that can demonstrate the ability to exit the facility unassisted in two minutes or less, and meet the requirements listed in Utah Administrative Code, R501-2-11, Emergency Plans, may receive approval from the Office of Licensing, Utah Department of Human Services, to remain in the facility as a resident.

3.4.9.1 In those facilities where the Office of Licensing, Department of Human Services, determines that the resident cannot exit the facility unassisted in two minutes or less, the facility management shall complete one of the following:

3.4.9.1.1 Make accommodations, changes or enact an emergency plan that guarantees the exiting of the resident in two minutes or less.

3.4.9.1.2 Provide a staff to resident ratio of one to one on a 24 hour basis.

3.4.9.1.3 Install an approved automatic fire sprinkler system.

3.4.9.1.4 Move the resident from the facility.

 

KEY: assisted living facilities

Date of Enactment or Last Substantive Amendment: [ March 10, 2009 ] October 8, 2010

Notice of Continuation: June 4, 2007

Authorizing, and Implemented or Interpreted Law: 53-7-204

 


Additional Information

The Portable Document Format (PDF) version of the Bulletin is the official version. The PDF version of this issue is available at https://rules.utah.gov/publicat/bull-pdf/2010/b20100901.pdf. The HTML edition of the Bulletin is a convenience copy. Any discrepancy between the PDF version and HTML version is resolved in favor of the PDF version.

Text to be deleted is struck through and surrounded by brackets (e.g., [example]). Text to be added is underlined (e.g., example).  Older browsers may not depict some or any of these attributes on the screen or when the document is printed.

For questions regarding the content or application of this rule, please contact Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at [email protected].