File No. 35401

This rule was published in the November 15, 2011, issue (Vol. 2011, No. 22) of the Utah State Bulletin.


Public Safety, Fire Marshal

Rule R710-6

Liquefied Petroleum Gas Rules

Notice of Proposed Rule

(Amendment)

DAR File No.: 35401
Filed: 11/01/2011 03:30:37 PM

RULE ANALYSIS

Purpose of the rule or reason for the change:

The Utah Liquefied Petroleum Gas Board met on 10/14/2011, in a regularly scheduled Board meeting and unanimously voted to update the currently adopted reference, National Fire Protection Association (NFPA), Standard 58, Liquefied Petroleum Gas Code, 2008 edition, to the 2011 edition.

Summary of the rule or change:

A summary of the proposed rule amendments are as follows: 1) in Subsection R710-6-1(1.1), the Board proposes to update the currently adopted 2008 edition of NFPA, Standard 58, Liquefied Petroleum Gas Code, to the 2011 edition; and 2) in Subsections R710-6-8(8.6.1) through (8.6.7), the Board proposes to amend several sections with regard to numbering to match the numerical sequence of the 2011 edition of the NFPA standard.

State statutory or constitutional authorization for this rule:

  • Section 53-7-305

This rule or change incorporates by reference the following material:

  • Updates Liquefied Petroleum Gas Code, published by National Fire Protection Association, 08/25/2010

Anticipated cost or savings to:

the state budget:

The only aggregate anticipated cost to the state budget would be to purchase the newly updated 2011 edition of NFPA 58 at $43 each and the full standard at $122 each. The aggregate anticipated cost for the needed standards would be approximately $800.

local governments:

There is no aggregate anticipated cost or savings to local government because these proposed amendments do not affect local government or local government's functions in any way.

small businesses:

There would be an aggregate anticipated cost to small businesses of approximately $400 per LP Gas container to monitor and test the cathodic protection on these containers. The testing on new LP Gas underground or mounded containers are required upon installation, 12 to 18 months later, and then every 3 years after that. The agency has no possible way of knowing how many containers will be installed after the adoption of this standard, and no way of being able to compute an aggregate amount with the alternating testing required.

persons other than small businesses, businesses, or local governmental entities:

There would now be a cost of approximately $400 per cathodic protection examination. These would be required at the time of installation, 12 to 18 months after installation, and every 3 years thereafter. This would only apply to those persons who owned an LP Gas container and it was mounded or underground.

Compliance costs for affected persons:

The compliance cost for affected persons would be approximately $400 per underground or mounded container to complete a cathodic protection examination for proper protection.

Comments by the department head on the fiscal impact the rule may have on businesses:

There would be no fiscal impact on LP Gas businesses for the enactment of these proposed rule amendments. The LP Gas companies that would be conducting these required tests would be passing the cost of the cathodic protection monitoring onto the owner of the new installation. If the new owner of the LP Gas container was a business, there would be a charge of approximately $400 per test to make sure the cathodic protection was adequate. No cathodic protection would allow the ground to deteriorate the metal container and the container leaking would become a public safety hazard.

Lance Davenport, Commissioner

The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

Public Safety
Fire MarshalRoom 302
5272 S COLLEGE DR
MURRAY, UT 84123-2611

Direct questions regarding this rule to:

  • Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov

Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

12/15/2011

This rule may become effective on:

12/22/2011

Authorized by:

Brent Halladay, State Fire Marshal

RULE TEXT

R710. Public Safety, Fire Marshal.

R710-6. Liquefied Petroleum Gas Rules.

R710-6-1. Adoption, Title, Purpose and Scope.

Pursuant to Title 53, Chapter 7, Section 305, Utah State Code Annotated 1953, the Liquefied Petroleum Gas (LPG) Board adopts minimum rules to provide regulation to those who distribute, transfer, dispense or install LP Gas and/or its appliances in the State of Utah.

There is adopted as part of these rules the following codes which are incorporated by reference:

1.1 National Fire Protection Association (NFPA), Standard 58, LP Gas Code, [2008]2011 edition, except as amended by provisions listed in R710-6-8, et seq.

1.2 National Fire Protection Association (NFPA), Standard 54, National Fuel Gas Code, 2009 edition, except as amended by provisions listed in R710-6-8, et seq.

1.3 National Fire Protection Association (NFPA), Standard 1192, Standard on Recreational Vehicles, 2008 Edition, except as amended by provisions listed in R710-6-8, et seq.

1.4 International Fire Code (IFC), Chapter 38, 2009 edition, as published by the International Code Council, Inc. (ICC), and as enacted and amended by the Utah State Legislature in Sections 102 and 201 of the State Fire Code Adoption Act.

1.5 A copy of the above codes are on file with the Division of Administrative Rules, and the State Fire Marshal's Office. The definitions contained in the afore referenced codes shall also pertain to these rules.

1.6 Title.

These rules shall be known as "Rules Governing LPG Operations in the State of Utah" and may be cited as such, and will be hereinafter referred to as "these rules".

1.7 Validity.

If any article, section, subsection, sentence, clause, or phrase, of these rules is, for any reason, held to be unconstitutional, contrary to statute, or exceeding the authority of the LPG Board such decision shall not affect the validity of the remaining portion of these rules.

1.8 Conflicts.

In the event where separate requirements pertain to the same situation in the same code, or between different codes or standards as adopted, the more restrictive requirement shall govern, as determined by the enforcing authority.

 

R710-6-8. Amendments and Additions.

The following amendments and additions are hereby adopted by the Board:

8.1 All LP Gas facilities that are located in a public place shall be inspected by a certified LP Gas serviceman every five (5) years for leaks in all buried piping as follows:

8.1.1 All buried piping shall be pressure tested and inspected for leaks as set forth in NFPA Standard 54, Sections 4.1.1 through 4.3.4.

8.1.2 If a leak is detected and repaired, the buried piping shall again be pressure tested for leaks.

8.1.3 The certified LP Gas serviceman shall keep a written record of the inspection and all corrections made to the buried piping located in a public place.

8.1.4 The inspection records shall be available to be inspected on a regular basis by the Division.

8.2 Whenever the Division is required to complete more than two inspections to receive compliance on an LP Gas System, container, apparatus, appliance, appurtenance, tank or tank trailer, or any pertinent equipment for the storage, transportation or dispensation of LP Gas, the Division shall charge to the owner for each additional inspection, the re-inspection fee as stated in R710-6-6.1(e).

8.3 All LP Gas containers of more than 5000 water gallons shall be inspected at least biannually for compliance with the adopted statute and rules. The following containers are exempt from this requirement:

8.3.1 Those excluded from the act in UCA, Section 53-7-303.

8.3.2 Containers under federal control.

8.3.3 Containers under the control of the U.S. Department of Transportation and used for transportation of LP Gas.

8.3.4 Containers located at private residences.

8.4 Those using self-serve key or card services shall be trained in safe filling practices by the licensed dealer providing the services. A letter shall be sent to the Division by the licensed dealer stating that those using the self-serve key or card service have been trained.

8.5 IFC Amendments:

8.5.1 IFC, Chapter 38, Section 3801.2 Permits. On line 2 after the word "105.7" add "and the adopted LPG rules".

8.5.2 IFC, Chapter 38, Section 3803.1 is deleted and rewritten as follows: General. LP Gas equipment shall be installed in accordance with NFPA 54, NFPA 58, the adopted LP Gas Administrative Rules, and the International Fuel Gas Code, except as otherwise provided in this chapter.

8.5.3 IFC, Chapter 38, Section 3809.12 is deleted and rewritten as follows: In Table 3809.12, Doorway or opening to a building with two or more means of egress, with regard to quantities 720 or less and 721-2,500, the currently stated "5" is deleted and replaced with "10".

8.5.4 IFC, Chapter 38, Section 3810.1 is amended as follows: On line two after the word "discontinued" add the words "for more than one year or longer as allowed by the Authority Having Jurisdiction (AHJ)".

8.6 NFPA, Standard 58 Amendments:

8.6.1 NFPA, Standard 58, Section 5.2.1.1 is amended to add the following section: [(c)](d) All new, used or existing containers of 5000 water gallons or less, installed in the State of Utah or relocated within the State of Utah shall be marked with the ASME stamp as defined in Section 2.1 of these rules. All new, used or existing containers of more than 5000 water gallons, installed in the State of Utah or relocated within the State of Utah, shall be marked with the ASME stamp as defined in Section 2.1 of these rules, and shall be inspected for approval by the Division. If the Division has concerns about the integrity or condition of the container, additional nondestructive testing may be required to include but not limited to hydrostatic testing, ultrasonic metal thickness testing or any other testing as determined necessary by the Division. All incurred costs for additional testing required by the Division shall be the responsibility of the owner.

8.6.2 NFPA, Standard 58, Section 5.2.1.1 is amended to add the following section: [(d)](e) If an existing U68, U69, U200 or U201 specification container, more than 5000 water gallons, is relocated within the State of Utah, and does not bear the required ASME stamp as defined in Section 2.1 of these rules, the container cannot be reinstalled unless the container has received a "Special Classification Permit" from the Division. Specifications of the type of container, container history if known, material specifications and calculations, and condition of the container shall be submitted to the Division by the person seeking the "Special Classification Permit". The Division shall inspect the container for approval. If the Division has concerns about the integrity or condition of the container, additional nondestructive tests such as hydrostatic testing, ultrasonic metal thickness testing or any other testing as determined necessary by the Division. All incurred costs of testing and evaluations shall be the responsibility of the owner. The Division will approve or disapprove the proposed container. Approval by the Division shall be obtained before the container is set or filled with LP Gas.

8.6.3 NFPA, Standard 58, Section 5.2.1.[5]6 is amended to add the following sentence at the end of the section:

(A) Repairs and alterations shall only be made by those holding a National Board "R" Certificate of Authorization commonly known as an R Stamp.

8.6.4 NFPA Standard 58, Sections 5.9.3.2([3]2)(a) and (b) are deleted and rewritten as follows:

Type K copper tubing without joints below grade may be used in exterior LP Gas piping systems only.

8.6.5 NFPA, Standard 58, Section 6.6.1.2 is amended to add the following at the end of the section: When guard posts are installed they shall be installed meeting the following requirements:

8.6.5.1 Constructed of steel not less than four inches in diameter and filled with concrete.

8.6.5.2 Set with spacing not more than four feet apart.

8.6.5.3 Buried three feet in the ground in concrete not less than 15 inches in diameter.

8.6.5.4 Set with the tops of the posts not less than three feet above the ground.

8.6.6 NFPA, Standard 58, Section 6.6.3 is amended to add the following section: 6.6.3.9 Skid mounted ASME horizontal containers greater than 2000 water gallons, with non-fireproofed steel mounted attached supports, resting on concrete, pavement, gravel or firm packed earth, may be mounted on the attached supports to a maximum of 12 inches from the top of the skid to the bottom of the container.

8.6.7 NFPA, Standard 58, Section 6.6.6 is amended to add the following: ([L]P) All metallic equipment and components that are buried or mounded shall have cathodic protection installed to protect the metal and shall meet the following requirements:

8.6.7.1 Sacrificial anodes shall be installed as required by the size of the container. If more than one sacrificial anode is required they shall be evenly distributed around the container.

8.6.7.2 Sacrificial anodes shall be connected to the container or piping as recommended by the manufacturer or using accepted engineering practices.

8.6.7.3 Sacrificial anodes shall be placed as near the bottom of the container as possible and approximately two feet away from the container.

8.6.8 NFPA, Standard 58, Section 6.24.3.16 is added as follows: On dispensing installations, 1000 gallon water capacity or less, where the dispensing cabinet is located next to the LP Gas container, stainless steel wire braid hose of more than 36 inches in length may be used on vapor and liquid return lines only. The hose shall be secured and routed in a safe and professional manner, marked with the date of installation, and shall be replaced every five years from that installation date.

8.6.9 NFPA, Standard 58, Section 6.25.3.2, the last sentence of the section is deleted and rewritten as follows: Existing installations shall comply with this requirement by March 31, 2011.

8.6.10 NFPA, Standard 58, Section 8.4.1.1(1) is amended as follows: On line one remove "5ft (1.5m)" and replace it with "10 ft (3m)".

 

KEY: liquefied petroleum gas

Date of Enactment or Last Substantive Amendment: [April 21, 2011]December 22, 2011

Notice of Continuation: March 16, 2011

Authorizing, and Implemented or Interpreted Law: 53-7-305

 


Additional Information

The Portable Document Format (PDF) version of the Bulletin is the official version. The PDF version of this issue is available at https://rules.utah.gov/publicat/bull-pdf/2011/b20111115.pdf. The HTML edition of the Bulletin is a convenience copy. Any discrepancy between the PDF version and HTML version is resolved in favor of the PDF version.

Text to be deleted is struck through and surrounded by brackets (e.g., [example]). Text to be added is underlined (e.g., example).  Older browsers may not depict some or any of these attributes on the screen or when the document is printed.

For questions regarding the content or application of this rule, please contact Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov.