File No. 35447

This rule was published in the December 1, 2011, issue (Vol. 2011, No. 23) of the Utah State Bulletin.


Environmental Quality, Environmental Response and Remediation

Rule R311-201

Underground Storage Tanks: Certification Programs and UST Operator Training

Notice of Proposed Rule

(Amendment)

DAR File No.: 35447
Filed: 11/15/2011 03:05:43 PM

RULE ANALYSIS

Purpose of the rule or reason for the change:

The changes are made to allow individuals to contract with Underground Storage Tank (UST) owners to act as a Class B operator without becoming a certified UST inspector. UST inspectors act under the direction of the Executive Secretary (UST) to perform inspections of UST facilities to determine their level of compliance with the UST rules and regulations. Because UST operator inspections are not done to determine the level of compliance, and are not done under the direction of the Executive Secretary, the requirements for UST inspectors are changed to refer directly to the statutory citation allowing the Executive Secretary to authorize employees or representatives to conduct UST inspections. This allows individuals who can demonstrate knowledge, training, and competency equivalent to an UST inspector to become third-party Class B operators. Individuals who are certified as general installers or installer technicians typically have achieved these levels of training and expertise, and it is appropriate to allow them to qualify as third-party Class B operators. Individuals who take training equivalent to that required for an UST inspector, and can demonstrate an appropriate level of acceptable financial responsibility through insurance, also will be able to qualify as third-party Class B operators.

Summary of the rule or change:

In Subsection R311-201-2(b), modifies the requirement for certification of UST inspectors to refer to the statutory citation (Subsection 19-6-404(2)(c)) that gives the Executive Secretary (UST) the authority to conduct UST inspections to determine compliance. In Subsection R311-201-12(e), changes the requirements for an individual who is not an owner or employee to act as a Class B operator. In Subsection R311-201-12(f), changes the requirements for individuals who contract to act as Class B operators. Two groups may qualify as third-party Class B operators: those who are certified as a general UST installer or UST installer technician, and those who meet the training requirements for a UST inspector and document an appropriate level of financial responsibility through liability insurance.

State statutory or constitutional authorization for this rule:

  • Section 63G-4-503
  • Sections 63G-4-201 through 63G-4-205
  • Section 19-6-402
  • Section 19-1-301
  • Section 63G-4-102
  • Section 19-6-105
  • Section 19-6-403

Anticipated cost or savings to:

the state budget:

No anticipated costs or savings. The rule broadens qualifications for individuals qualified to provide services as a Third-party Class B Operator. There are no costs or savings associated with these changes.

local governments:

No costs are anticipated, but there may be some savings resulting from this change for local governments that own regulated underground storage tanks. This change broadens the population of individuals who qualify to provide services as a third-party Class B Operator. The increase in the number of individuals who provide these services may reduce the cost for those local governments that choose to meet the operator training requirement by outsourcing this service. The total savings would depend on the level of cost reduction achieved by increased competition among third-party Class B operators and the number of tank owners who would contract for the service.

small businesses:

No costs are anticipated but there may be some savings resulting from this change for small businesses that own regulated underground storage tanks. This change broadens the population of individuals who qualify to provide services as a third-party Class B Operator. The increase in the number of individuals who provide these services may reduce the cost for those businesses that choose to meet the operator training requirement by outsourcing this service. The total savings would depend on the level of cost reduction achieved by increased competition among third-party Class B operators and the number of tank owners who would contract for the service. In addition, some small businesses may have employees that will qualify as third-party Class B Operators and may expand their business operations to offer these services for a fee. If this occurs, the businesses would save the cost of becoming a UST inspector (approximately $600). Aggregate savings would depend on the number of individuals who would qualify as third-party Class B Operators.

persons other than small businesses, businesses, or local governmental entities:

No costs are anticipated but there may be some savings resulting from this change for persons other than small businesses, businesses, or local government entities. This change broadens the population of individuals who qualify to provide services as a third-party Class B Operator. The increase in the number of individuals who provide these services may reduce the cost for those entities that choose to meet the operator training requirement by outsourcing this service. The total savings would depend on the level of cost reduction achieved by increased competition among third-party Class B operators and the number of tank owners who would contract for the service. In addition, some businesses may have employees that will qualify as third-party Class B Operators and may expand their business operations to offer these services for a fee. If this occurs, the businesses would save the cost of becoming a UST inspector (approximately $600). Aggregate savings would depend on the number of individuals who would qualify as third-party Class B Operators.

Compliance costs for affected persons:

The proposed change allows individuals to qualify to be third-party Class B operators without the cost of becoming a UST inspector (approximately $600). The cost of training and registration as a Class B operator (approximately $250) is already in place and will not change from this rule change. An individual who wants to become a third-party Class B Operator will have the cost of training, either the inspector-equivalent training or training to become a general installer or installer technician. An individual who qualifies by taking the inspector-equivalent training would also have to pay the costs to acquire financial responsibility coverage in the form of liability insurance. In reality, most individuals who are likely to qualify as third-party Class B Operators already are certified as a general installer or technician, so there would be no additional expense for those individuals to register as a third Party Class B Operator.

Comments by the department head on the fiscal impact the rule may have on businesses:

These changes should not have any material fiscal impact on businesses. They will provide a way for individuals who are already trained and have experience in installing and servicing underground storage tank systems and associated equipment to be able to contract with UST owners to provide the services of a Class B operator. They already have the necessary training, and would be able to qualify as a third-party Class B operator without having to incur the added expense to become a certified UST inspector.

Amanda Smith, Executive Director

The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

Environmental Quality
Environmental Response and RemediationRoom First Floor
195 N 1950 W
SALT LAKE CITY, UT 84116-3085

Direct questions regarding this rule to:

  • Gary Astin at the above address, by phone at 801-536-4103, by FAX at 801-359-8853, or by Internet E-mail at gastin@utah.gov

Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

01/03/2012

Interested persons may attend a public hearing regarding this rule:

  • 12/20/2011 01:30 PM, MSOB, 195 N 1950 W, Room 1015, Salt Lake City, UT

This rule may become effective on:

01/13/2012

Authorized by:

Brent Everett, Director

RULE TEXT

R311. Environmental Quality, Environmental Response and Remediation.

R311-201. Underground Storage Tanks: Certification Programs and UST Operator Training.

R311-201-1. Definitions.

Definitions are found in Rule R311-200.

 

R311-201-2. Certification Requirement.

(a) Certified UST Consultant. After December 31, 1995, no person shall provide or contract to provide information, opinions, or advice relating to UST release management, abatement, investigation, corrective action, or evaluation for a fee, or in connection with the services for which a fee is charged, without having certification to conduct these activities, except as outlined in Subsections 19-6-402(6)(b)(i), 19-6-402(6)(b)(ii) and R311-204-5(b). The Certified UST Consultant shall be the person directly overseeing UST release-related work. The Certified UST Consultant shall make pertinent project management decisions and be responsible for ensuring that all aspects of UST-related work are performed in an appropriate manner, and all related documentation for work performed submitted to the Executive Secretary shall contain the Certified UST Consultant's signature. After December 31, 1995, any release abatement, investigation, and corrective action work performed by a person who is not certified or who is not working under the direct supervision of a Certified UST Consultant, and is performed for compliance with Utah underground storage tank release-related rules, except as outlined in Subsections 19-6-402(6)(b)(i), 19-6-402(6)(b)(ii) and R311-204-5(b), may be rejected by the Executive Secretary.

(b) UST Inspector. After December 31, 1989, no person shall conduct underground storage tank inspection [for determining compliance with Utah underground storage tank rules]as authorized in Subsection 19-6-404(2)(c) without having certification to conduct these activities.[ After December 31, 1989, no owner or operator shall allow any underground storage tank inspections for determining compliance with Utah underground storage tank rules to be conducted on a tank under their ownership or operation unless the person conducting the tank inspection is certified according to Rule R311-201.]

(c) UST tester. After December 31, 1989, no person shall conduct UST testing without having certification to conduct such activities. After December 31, 1989, no owner or operator shall allow UST testing to be conducted on an UST under their ownership or operation unless the person conducting the UST testing is certified according to Rule R311-201. Certification by the Executive Secretary under this Rule for tank, line and leak detector testing shall apply only to the specific UST testing equipment and procedures for which the UST tester has been successfully trained by the manufacturer of the equipment or by training determined by the Executive Secretary to be equivalent to the manufacturer training. The Executive Secretary may issue a limited certification restricting the type of UST testing the applicant can perform.

(d) Groundwater and soil sampler. After December 31, 1989, no person shall conduct groundwater or soil sampling for determining levels of contamination which may have occurred from regulated underground storage tanks without having certification to conduct these activities. After December 31, 1989, no owner or operator shall allow any groundwater or soil sampling for determining levels of contamination which may have occurred from regulated underground storage tanks to be conducted on a tank under their ownership or operation unless the person conducting the groundwater or soil sampling is certified according to Rule R311-201.

(e) UST Installer. After January 1, 1991, no person shall install an underground storage tank without having certification or the on-site supervision of an individual having certification to conduct these activities. After January 1, 1991, no owner or operator shall allow the installation of an underground storage tank to be conducted on a tank under their ownership or operation unless the person installing the tank is certified according to Rule R311-201. The Executive Secretary may issue a limited certification restricting the type of UST installation the applicant can perform.

(f) UST Remover. After January 1, 1991, no person shall remove an underground storage tank without having certification or the on-site supervision of an individual having certification to conduct these activities. After January 1, 1991, no owner or operator shall allow the removal of an underground storage tank to be conducted on a tank under their ownership or operation unless the person conducting the tank removal is certified according to Rule R311-201.

 

. . . . . . .

 

R311-201-12. UST Operator Training and Registration.

(a) To meet the Operator Training requirement (42 USC Section 6991i) of the Solid Waste Disposal Act as amended by the Energy Policy Act of 2005, each UST facility shall, by January 1, 2012, have UST facility operators that are trained and registered according to the requirements of this section. Each facility shall have three classes of operators: A, B, and C.

(1) A facility may have more than one person designated for each operator class.

(2) An individual acting as a Class A or B operator may do so for more than one facility.

(b) The UST owner or operator shall provide documentation to the Executive Secretary to identify the Class A, B, and C operators for each facility. If an owner or operator does not register and identify Class A, B, and C operators for a facility, the certificate of compliance for the facility may be revoked for failure to demonstrate substantial compliance with all state and federal statutes, rules and regulations.

(c) After January 1, 2012, new Class A and B operators shall be trained and registered within 30 days of assuming responsibility for an UST facility. New Class C operators shall be trained before assuming the responsibilities of a Class C operator.

(d) The Class A operator shall be an owner or employee who has primary responsibility for the broader aspects of the statutory and regulatory requirements and standards necessary to operate and maintain the UST system. The Class A operator shall:

(1) have a general knowledge of UST systems;

(2) ensure that UST records are properly maintained according to 40 CFR 280;

(3) ensure that yearly UST fees are paid;

(4) ensure proper response to and reporting of emergencies caused by releases or spills from USTs;

(5) make financial responsibility documents available to the Executive Secretary as required; and

(6) ensure that Class B and Class C operators are trained and registered.

(e) The Class B operator shall implement routine daily aspects of operation, maintenance, and recordkeeping for UST systems. The Class B operator shall be an owner, employee, or [contractor working for the UST owner or]third-party Class B operator. The Class B operator shall:

(1) ensure that on-site UST operator inspections are conducted according to the requirements of Subsection R311-201-12(h);

(2) ensure that UST release detection is performed according to 40 CFR 280 subpart D;

(3) ensure that the status of the UST system is monitored every seven days for alarms and unusual operating conditions that may indicate a release;

(4) document the reason for an alarm or unusual operating condition identified in Subsection R311-201-12(e)(3), if it is not reported as a suspected release according to 40 CFR 280.50;

(5) ensure that appropriate release detection and other records are kept according to 40 CFR 280.34 and 280.45, and are made available for inspection;

(6) ensure that spill prevention, overfill prevention, and corrosion protection requirements are met;

(7) be on site for facility compliance inspections, or designate another individual to be on site for inspections;

(8) ensure that suspected releases are reported according to the requirements of 40 CFR 280.50; and

(9) ensure that Class C operators are trained and registered, and are on-site during operating hours.

(f) [An individual who contracts to act as a Class B operator for an UST owner or operator, or performs UST operator inspections according to Subsection R311-201-12(h), and is not the owner or operator, or an employee of the owner or operator, shall be certified as an UST inspector according to Section R311-201-2, and shall meet all requirements of an UST inspector.]After January 1, 2012, any individual providing services as a third-party Class B operator shall be trained and registered in accordance with Subsection R311-201-12(j) and shall:

(1) be a current certified UST installer as either a general installer or service/repair technician, or

(2) meet the training requirements of a certified UST inspector and document comprehensive or general liability insurance with limits of $250,000 minimum per occurrence.

(g) The Class C operator is an employee and is generally the first line of response to events indicating emergency conditions. A Class C operator shall:

(1) be present at the facility at all times during normal operating hours;

(2) monitor product transfer operations according to 40 CFR 280.30(a), to ensure that spills and overfills do not occur;

(3) properly respond to alarms, spills, and overfills;

(4) notify Class A and/or Class B operators and appropriate emergency responders when necessary; and

(5) act in response to emergencies and other situations caused by spills or releases from an UST system that pose an immediate danger or threat to the public or to the environment, and that require immediate action.

(h) UST Operator Inspections.

(1) Each UST facility shall have an on-site operator inspection conducted every 30 days, or as approved under Subsection R311-201-12(h)(4) or (5). The inspection shall be performed by or under the direction of the designated Class B operator. The Class B operator shall ensure that documentation of each inspection is kept and made available for review by the Executive Secretary.

(2) The UST operator inspection shall document that:

(A) release detection systems are properly operating and maintained;

(B) spill, overfill, vapor recovery, and corrosion protection systems are in place and operational;

(C) tank top manways, tank and dispenser sumps, secondary containment sumps, and under-dispenser containment are intact, and are properly maintained to be free of water, product, and debris;

(D) the tag or other identifying method issued under Subsection 19-6-411(7) is properly in place on each tank;

(E) alarm conditions that could indicate a release are properly investigated and corrected, and are reported as suspected releases according to 40 CFR 280.50 or documented to show that no release has occurred; and

(F) unusual operating conditions and other indications of a release or suspected release indicated in 40 CFR 280.50 are properly reported.

(3) The individual conducting the inspection shall use the form "UST Operator Inspection- Utah" to conduct on-site operator inspections. The form, dated April 30, 2009, and including information required to be completed during the inspection, is hereby incorporated by reference.

(4) The Executive Secretary may allow operator inspections to be performed less frequently in situations where it is impractical to conduct an inspection every 30 days. The owner or operator shall request the exemption, justify the reason for the exemption, and submit a plan for conducting operator inspections at the facility.

(5) An UST facility whose tanks are properly temporarily closed according to 40 CFR 280.70 and R311-204-4 shall have an operator inspection every 90 days.

(i) A facility that normally has no employee or other responsible person on site, or is open to dispense fuel at times when no employee or responsible person is on site, shall have:

(1) a sign posted in a conspicuous place, giving the name and telephone number of the facility owner, operator, or local emergency responders, and

(2) an emergency shutoff device, if the facility dispenses fuel.

(j) Operator Training and Registration

(1) Training and testing.

(A) Applicants for Class A and B operator registration shall successfully complete an approved operator training course within the six-month period prior to application.

(B) The training course shall be approved by the Executive Secretary, and shall include instruction in the following: notification, temporary and permanent closure, installation permitting, underground tank requirements of the 2005 Energy Policy Act, Class A, B, and C operator responsibilities, spill prevention, overfill prevention, UST release detection, corrosion protection, record-keeping requirements, emergency response, product compatibility, Utah UST rules and regulations, UST financial responsibility, and delivery prohibition.

(C) Applicants for Class A and B operator registration shall successfully pass a registration examination authorized by the Executive Secretary. The Executive Secretary shall determine the content of the examination.

(D) An individual applying for Class A or B operator registration may be exempted from meeting the requirements of Subsections R311-201-12(j)(1)(A) and (C) by completing the following within the six-month period prior to application:

(i) successfully passing a nationally recognized UST operator examination approved by the Executive Secretary, and

(ii) successfully passing a Utah UST rules and regulations examination authorized by the Executive Secretary. The Executive Secretary shall determine the content of the examination.

(E) Class C operators shall receive instruction in product transfer procedures, emergency response, and initial response to alarms and releases.

(2) Registration application.

(A) Applicants for Class A and B operator registration shall submit a registration application to the Executive Secretary, shall document proper training, and shall pay any applicable fees.

(B) Class C operators shall be designated by a Class B operator. The Class B operator shall maintain a list identifying the Class C operators for each UST facility. The list shall identify each Class C operator, the date of training, and the trainer. Identification on the list shall serve as the operator registration for Class C operators.

(C) A registered Class A or B operator may act as a Class C operator by meeting the training and registration requirements for a Class C operator.

(D) Class A and B registration shall be effective for a period of three years, and shall not lapse or expire if the registered operator leaves the employment of the company under which the registration was obtained.

(3) Renewal of registration.

(A) Class A and B operators shall apply for renewal of registration not more than six months prior to the expiration of the registration by:

(i) submitting a completed application form;

(ii) paying any applicable fees; and

(iii) documenting successful completion of any re-training required by Subsection R311-201-12(k).

(B) If the Executive Secretary determines that the operator meets all the requirements for registration, the Executive Secretary shall renew the applicant's registration for a period equal to the initial registration.

(C) Any applicant for renewal who has a registration that has been expired for more than two years prior to submitting a renewal application shall successfully satisfy the training and examination requirements for initial registration under Subsection R311-201-12(j)(1) before receiving the renewal registration.

(k) Re-training.

(1) A Class A operator shall be subject to re-training requirements if any facility for which the Class A operator has oversight is found to be out of compliance due to:

(A) lapsing of certificate of compliance;

(B) failure to provide acceptable financial responsibility; or

(C) failure to ensure that Class B and C operators are trained and registered.

(2) A Class B operator shall be subject to re-training requirements if a facility for which the Class B operator has oversight is found to be out of compliance due to:

(A) failure to document significant operational compliance, as determined by the EPA Release Prevention Compliance Measures Matrix and Release Detection Compliance Measures Matrix, both incorporated by reference in Subsection R311-206-10(b)(1);

(B) failure to perform UST operator inspections required by Subsection R311-201-12(h);

(C) failure to have the tag or other identifying method issued under Subsection 19-6-411(7) properly in place on each tank; or

(D) failure to ensure that Class C operators are trained and registered, and are on-site during operating hours.

(3) To be re-trained, Class A and Class B operators shall successfully complete the appropriate Class A or B operator training course and examination, or shall complete an equivalent re-training course and examination approved by the Executive Secretary.

(4) Class A and B operators shall be re-trained within 90 days of the date of the determination of non-compliance, and shall submit documentation showing successful completion of the re-training to the Executive Secretary within 30 days of the re-training. If the documentation is not received, the Executive Secretary may revoke the certificate of compliance for the facility for failure to demonstrate substantial compliance with all state and federal statutes, rules and regulations.

(5) If the documentation of re-training is not received by the Executive Secretary within six months of the date of determination of non-compliance, the Class A or B operator's registration will lapse. To re-register, the operator shall meet the requirements of Subsection R311-201-12(j)(1) and (2).

(6) If a facility for which a Class A or B operator has oversight is found to be out of compliance under Subsections R311-201-12(k)(1) or (2), re-training shall not be required if the Class A or B operator successfully completes and documents re-training under Subsections R311-201-12(k)(3) and (4) for a prior determination of non-compliance that occurred during the previous nine months.

(l) Reciprocity.

(1) If the Executive Secretary determines that another state's operator training program is equivalent to the operator training program provided in this rule, he may accept an applicant's Class A or Class B registration application, provided that the applicant:

(A) submits a completed application form;

(B) passes the Utah UST rules and regulations examination referenced in Subsection R311-201-12(j)(1)(D)(ii), and

(C) submits payment of any applicable registration fees.

(2) The Class A or Class B registration shall be valid until the Utah registration expiration described in Subsection R311-201-12(j)(2)(D).

 

KEY: hazardous substances, administrative proceedings, underground storage tanks, revocation procedures

Date of Enactment or Last Substantive Amendment: [August 29, 2011]2012

Notice of Continuation: April 18, 2007

Authorizing, and Implemented or Interpreted Law: 19-1-301; 19-6-105; 19-6-402; 19-6-403; 63G-4-102; 63G-4-201 through 205; 63G-4-503

 


Additional Information

The Portable Document Format (PDF) version of the Bulletin is the official version. The PDF version of this issue is available at https://rules.utah.gov/publicat/bull-pdf/2011/b20111201.pdf. The HTML edition of the Bulletin is a convenience copy. Any discrepancy between the PDF version and HTML version is resolved in favor of the PDF version.

Text to be deleted is struck through and surrounded by brackets (e.g., [example]). Text to be added is underlined (e.g., example).  Older browsers may not depict some or any of these attributes on the screen or when the document is printed.

For questions regarding the content or application of this rule, please contact Gary Astin at the above address, by phone at 801-536-4103, by FAX at 801-359-8853, or by Internet E-mail at gastin@utah.gov.