File No. 33575
This rule was published in the May 15, 2010, issue (Vol. 2010, No. 10) of the Utah State Bulletin.
Public Safety, Fire Marshal
Rule R710-9
Rules Pursuant to the Utah Fire Prevention Law
Notice of Proposed Rule
(Amendment)
DAR File No.: 33575
Filed: 04/26/2010 12:55:19 PM
RULE ANALYSIS
Purpose of the rule or reason for the change:
During the 2010 session of the Utah State Legislature, H.B. 308 was sponsored and passed by the legislature adopting the 2009 edition of the International Fire Code and a number of amendments and additions to the fire code. The newly adopted statute adopting the state fire code by the legislature rather than the Utah Fire Prevention Board by administrative rule, will go into effect on 07/01/2010. To maintain the proper transition of authority, the administrative rule is proposed to be amended to delete all portions of the rule that referenced the adoption of the fire code, adoption of incorporated references, and all amendments and additions to the currently adopted 2006 International Fire Code. (DAR NOTE: H.B. 308 (2010) is found at Chapter 335, Laws of Utah 2010, and will be effective 07/01/2010.)
Summary of the rule or change:
A summary of the proposed rule amendments are as follows: 1) in Section R710-9-1, it is proposed to eliminate the adoption of the 2006 International Fire Code and nine other standards that were adopted by incorporated reference; 2) in Section R710-9-2, several definitions that will no longer be applicable are proposed to be eliminated; and 3) in Section R710-9-6, the entire amendments and additions section amending the 2006 International Fire Code is proposed to be eliminated from the rule as it will now be in the adopted statute.
State statutory or constitutional authorization for this rule:
- Section 53-7-204
Anticipated cost or savings to:
the state budget:
There is no aggregate anticipated cost or savings to the state budget because this proposed rule amendment is eliminating no longer needed sections of the administrative rule that will now be adopted by statute.
local governments:
There is no aggregate anticipated cost or savings to local government because this proposed rule amendment is eliminating no longer needed sections of the administrative rule that will now be adopted by statute.
small businesses:
There is no aggregate anticipated cost or savings to small businesses because this proposed rule amendment is eliminating no longer needed sections of the administrative rule that will now be adopted by statute.
persons other than small businesses, businesses, or local governmental entities:
There is no aggregate anticipated cost or savings to other persons because this proposed rule amendment is removing portions of an administrative rule that will no longer be in effect after 07/01/2010, due to the adoption of the state fire code statute.
Compliance costs for affected persons:
There is no compliance costs for affected persons due to this proposed administrative rule amendment because this proposed rule amendment removes the adoption of the 2006 International Fire Code, adopted incorporated references, and any amendments and additions that were made to the currently adopted fire standard.
Comments by the department head on the fiscal impact the rule may have on businesses:
During the 2009 and 2010 legislative sessions, the Legislature by statute removed the adoption of the state fire code from the authority of the Utah Fire Prevention Board, and made it the responsibility of the state legislature. There is no fiscal impact to businesses for the enactment of these proposed rule amendments because they do not affect businesses in any way.
D. Lance Davenport, Commissioner
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Public SafetyFire Marshal
5272 S COLLEGE DR
MURRAY, UT 84123-2611
Direct questions regarding this rule to:
- Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at [email protected]
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
06/14/2010
This rule may become effective on:
07/01/2010
Authorized by:
Ron Morris, Utah State Fire Marshal
RULE TEXT
R710. Public Safety, Fire Marshal.
R710-9. Rules Pursuant to the Utah Fire Prevention Law.
R710-9-1. Title, Authority, and Adoption of Codes.
1.1 These rules shall be known as the "Rules Pursuant to the Utah Fire Prevention Law", and may be cited as such, and will be hereafter referred to as "these rules".
1.2 These rules are promulgated in accordance with Title 53, Chapter 7, Section 204, Utah Code Annotated 1953, as amended.
1.3 These rules are adopted by the Utah
Fire Prevention Board to provide minimum rules for safeguarding
life and property from the hazards of fire and explosion, for board
meeting conduct, procedures to amend incorporated references, [establishing amendments and additions to the adopted
codes, ]establishing board subcommittees, enforcement of the
rules of the State Fire Marshal, and deputizing Special Deputy
State Fire Marshals.[
1.4 There is adopted as part of these rules the following
code which is incorporated by reference:
1.4.1 International Fire Code (IFC), 2006 edition, excluding
appendices, as promulgated by the International Code Council,
Inc., except as amended by provisions listed in R710-9-6, et
seq.
1.5 There is further adopted as part of these rules the
following codes which are also incorporated by reference and
supercede the adopted standards listed in the International Fire
Code, 2006 edition, Chapter 45, Referenced Standards, as
follows:
1.5.1 National Fire Protection Association (NFPA), NFPA 10,
Standard for Portable Fire Extinguishers, 2007 edition, except as
amended by provisions listed in R710-9-6, et seq.
1.5.2 National Fire Protection Association (NFPA), NFPA 13,
Standard for Installation of Sprinkler Systems, 2007 edition,
except as amended by provisions listed in R710-9-6, et seq.
1.5.3 National Fire Protection Association (NFPA), NFPA 13D,
Standard for the Installation of Sprinkler Systems in One and Two
Family Dwellings and Manufactured Homes, 2007 edition, except as
amended by provisions listed in R710-9-6, et seq.
1.5.4 National Fire Protection Association (NFPA), NFPA 13R,
Standard for the Installation of Sprinkler Systems in Residential
Occupancies up to and including Four Stories in Height, 2007
edition, except as amended by provisions listed in R710-9-6, et
seq.
1.5.5 National Fire Protection Association (NFPA), NFPA 70,
National Electric Code, 2008 edition, as adopted by the Uniform
Building Standards Act, Title 58. Chapter 56, Section 4, Utah
Code Annotated 1953 and the Utah Administrative Code R156-56-701.
Wherever there is a section, figure or table in the International
Fire Code (IFC) that references "ICC Electrical Code",
that reference shall be replaced with "National Electric
Code".
1.5.6 National Fire Protection Association (NFPA), NFPA 72,
National Fire Alarm Code, 2007 edition, except as amended in
provisions listed in R710-9-6, et seq.
1.5.7 National Fire Protection Association (NFPA), NFPA 101,
Life Safety Code, 2006 edition, except as amended in provisions
listed in R710-9-6, et seq. Wherever there is a section, figure
or table in NFPA 101 that references "NFPA 5000 - Building
Construction and Safety Code", that reference shall be
replaced with the "International Building Code".
1.5.8 National Fire Protection Association (NFPA), NFPA 160,
Standard for Flame Effects Before an Audience, 2006 edition,
except as amended by provisions listed in R710-9-6, et seq.
1.6 National Fire Protection Association (NFPA), NFPA 96,
Standard for Ventilation Control and Fire Protection of
Commercial Cooking Operations, 2008 edition,
except as amended by provisions listed in R710-9-6, et
seq.]
R710-9-2. Definitions.
[2.1 "Appreciable Depth" means a depth greater than
1/4 inch.
]2.[2]1 "Authority Having Jurisdiction (AHJ)" means
the State Fire Marshal, his authorized deputies, or the local fire
enforcement authority.
2.[3]2 "Board" means Utah Fire Prevention
Board.
2.[4]3 "Division" means State Fire Marshal.
[2.5 "ICC" means International Code Council,
Inc.
]2.[6]4 "IFC" means International Fire Code.
[2.7 "Institutional occupancy" means asylums, mental
hospitals, hospitals, sanitariums, homes for the aged, residential
health care facilities, children's homes or institutions, or
any similar institutional occupancy.
]2.[8]5 "LFA" means Local Fire Authority.
[2.9 "NFPA" means National Fire Protection
Association.
2.10 "Place of assembly" means where 50 or more
people gather together in a building, structure, tent, or room
for the purpose of amusement, entertainment, instruction, or
education.
]2.[11]6 "SFM" means State Fire Marshal or authorized
deputy.
2.[12]7 "Sub-Committee" means Fire Prevention Board
Budget Sub-Committee or Amendment Sub-Committee.
2.[13]8 "UCA" means Utah Code Annotated, 1953.
R710-9-3. Conduct of Board Members and Board Meetings.
3.1 Board meetings shall be presided over and conducted by the chairman and in his absence the vice chairman or the chairman's designee.
3.2 A quorum shall be required to approve any action of the Board.
3.3 The chairman of the Board and Board members shall be entitled to vote on all issues considered by the Board. A Board member who declares a conflict of interest or where a conflict of interest has been determined, shall not vote on that particular issue.
3.4 Meetings of the Board shall be conducted in accordance with an agenda, which shall be submitted to the members by the division, not less that 21 days before the regularly scheduled Board meetings.
3.5 Public notice of Board meetings shall be made by the Division as prescribed in UCA Section 52-4-6.
3.6 The division shall provide the Board with a secretary who shall prepare minutes and shall perform all secretarial duties necessary for the Board to fulfill its responsibility. The minutes of Board meetings shall be completed and sent to Board members at least 14 days prior to the scheduled Board meeting.
3.7 A Board members standing on the Board shall come under review after two unexcused absences in one year from regularly scheduled board meetings. The Board members name shall be submitted to the governors office for status review.
R710-9-4. Deputizing Persons to Act as Special Deputy State Fire Marshals.
4.1 Special deputy state fire marshals may be appointed by the SFM to positions of expertise within the regular scope of the Fire Marshal's Office.
4.2 Pursuant to Section 53-7-101 et seq., special deputy state fire marshals may also be appointed to assist the Fire Marshal's Office in establishing and maintaining minimum fire prevention standards in those occupancy classifications listed in the International Fire Code.
4.3 Special deputy state fire marshals shall be appointed after review by the State Fire Marshal in regard to their qualifications and the overall benefit to the Office of the State Fire Marshal.
4.4 Special deputy state fire marshals shall be appointed by completing an oath and shall be appointed for a specific period of time.
4.5 Special deputy state fire marshals shall have a picture identification card and shall carry that card when performing their assigned duties.
R710-9-5. Procedures to Amend the International Fire Code.
5.1 All requests for amendments to the IFC shall be submitted to the division on forms created by the division, for presentation to the Board at the next regularly scheduled Board meeting.
5.2 Requests for amendments received by the division less than 21 days prior to any regularly scheduled meeting of the Board may be delayed in presentation until the next regularly scheduled Board meeting.
5.3 Upon presentation of a proposed amendment, the Board shall do one of the following:
5.3.1 accept the proposed amendment as submitted or as modified by the Board;
5.3.2 reject the proposed amendment;
5.3.3 submit the proposed amendment to the Board Amendment Subcommittee for further study; or
5.3.4 return the proposed amendment to the requesting agency, accompanied by Board comments, allowing the requesting agency to resubmit the proposed amendment with modifications.
5.4 The Board Amendment Subcommittee shall report its recommendation to the Board at the next regularly scheduled Board meeting.
5.5 The Board shall make a final decision on the proposed amendment at the next Board meeting following the original submission.
5.6 The Board may reconsider any request for amendment, reverse or modify any previous action by majority vote.
5.7 When approved by the Board, the requesting agency shall provide to the division within 45 days, the completed ordinance.
5.8 The division shall maintain a list of amendments to the IFC that have been granted by the Board.
5.9 The division shall make available to any person or agency copies of the approved amendments upon request, and may charge a reasonable fee for multiple copies in accordance with the provisions of UCA, 63-2-203.
[R710-9-6. Amendments and Additions.
The following amendments and additions are hereby adopted by
the Board for application statewide:
6.1 International Fire Code - Administration
6.1.1 IFC, Chapter 1, Section 105.6.16 is amended to add the
following section: 11. The owner of an underground tank that is
out of service for longer than one year, shall receive a
Temporary Closure Notice from the Department of Environmental
Quality and a copy shall be given to the AHJ.
6.1.2 IFC, Chapter 1, Section 109.2 is amended as follows:
On line three after the words "is in violation of this
code," add the following "or other pertinent laws or
ordinances".
6.2 International Fire Code - Definitions
6.2.1 IFC, Chapter 2, Section 202, Educational Group E, Day
care is amended as follows: On line three delete the word
"five" and replace it with the word
"four".
6.2.2 IFC, Chapter 2, Section 202, Institutional Group I,
Group I-1 is amended to add the following: On line ten add
"Type 1" in front of the words "Assisted living
facilities".
6.2.3 IFC, Chapter 2 Section 202, Institutional Group I,
Group I-2 is amended as follows: On line four delete the word
"five" and replace it with the word "three".
On line eleven after the words "Detoxification
facilities" delete the rest of the section, and add the
following: "Ambulatory surgical centers with two or more
operating rooms where care is less than 24 hours, outpatient
medical care facilities for ambulatory patients (accommodating
more than five such patients in each tenant space) which may
render the patient incapable of unassisted self-preservation, and
Type 2 assisted living facilities. Type 2 assisted living
facilities with five or fewer persons shall be classified as a
Group R-4. Type 2 assisted living facilities with at least six
and not more than 16 residents shall be classified as a Group I-1
facility.
6.2.4 IFC, Chapter 2, Section 202, Institutional Group I,
Group I-4, day care facilities, Child care facility is amended as
follows: On line three delete the word "five" and
replace it with the word "four". Also on line two of
the Exception delete the word "five" and replace it
with the word "four".
6.2.5 IFC, Chapter 2, Section 202 General Definitions,
Occupancy Classification, Residential Group R-1 is amended to add
the following: Exception: Boarding houses accommodating 10
persons or less shall be classified as Residential Group
R-3.
6.2.6 IFC, Chapter 2, Section 202 General Definitions,
Occupancy Classification, Residential Group R-2 is amended to add
the following: Exception: Boarding houses accommodating 10
persons or less shall be classified as Residential Group
R-3.
6.3 International Fire Code - General Precautions Against
Fire
6.3.1 IFC, Chapter 3, Section 304.1.2 is amended as follows:
Delete the current line six and add the following in it's
place: "the Utah Administrative Code, R652-122-200, Minimum
Standards for Wildland Fire Ordinance."
6.3.2 IFC, Chapter 3, Section 311.1.1 is amended as follows:
On line ten delete the words "International Property
Maintenance Code and the" from this section.
6.3.3 IFC, Chapter 3, Section 311.5 is amended as follows:
On line two delete the word "shall" and replace it with
the word "may".
6.3.4 IFC, Chapter 3, Section 315.2.1 is amended to add the
following: Exception: Where storage is not directly below the
sprinkler heads, storage is allowed to be placed to the ceiling
on wall mounted shelves that are protected by fire sprinkler
heads in occupancies meeting classification as light or ordinary
hazard.
6.4 International Fire Code - Emergency Planning and
Preparedness
6.4.1 IFC, Chapter 4, Section 404.2(7) is amended as
follows: After the word "buildings" add "to
include sororities and fraternity houses".
6.5 International Fire Code - Building Services and
Systems
6.5.1 IFC, Chapter 6, Section 607.3 is deleted and rewritten
as follows: Firefighter service keys shall be kept in a
"Supra - Stor-a-key" elevator key box or similar box
with corresponding key system that is adjacent to the elevator
for immediate use by the fire department. The key box shall
contain one key for each elevator, one key for lobby control, and
any other keys necessary for emergency service. The elevator key
box shall be accessed using a 6049 numbered key. All existing
elevator key box locks that do not use the numbered 6049 key
shall be changed to the 6049 key by December 31, 2011.
6.5.2 IFC, Chapter 6, Section 609.1 is amended to add the
following: On line three after the word "Code" add the
words "and NFPA 96".
6.6 International Fire Code - Fire Protection Systems
6.6.1 IFC, Chapter 9, Section 901.2 is amended to add the
following: The code official has the authority to request record
drawings ("as builts") to verify any modifications to
the previously approved construction documents.
6.6.2 IFC, Chapter 9, Section 902.1 Definitions, RECORD
DRAWINGS is deleted and rewritten as follows: Drawings ("as
builts") that document all aspects of a fire protection
system as installed.
6.6.3 IFC, Chapter 9, Section 901.6 is amended to add the
following: The owner or administrator of each building shall
insure the inspection and testing of water based fire protection
systems as required in Rule R710-5, Automatic Fire Sprinkler
System Inspecting and Testing.
6.6.4 IFC, Chapter 9, Section 903.2.1.2 is amended to add
the following subsection: 4. An automatic fire sprinkler system
shall be provided throughout Group A-2 occupancies where indoor
pyrotechnics are used.
6.6.5 IFC, Chapter 9, Section 903.2.3(2) is deleted and
rewritten as follows: Where a Group F-1 fire area is located more
than three stories above the lowest level of fire department
vehicle access; or
6.6.6 IFC, Chapter 9, Section 903.2.6(2) is deleted and
rewritten as follows: Where a Group M fire area is located more
than three stories above the lowest level of fire department
vehicle access; or
6.6.7 IFC, Chapter 9, Section 903.2.7 Group R, is amended to
add the following: Exception: Detached one- and two-family
dwellings and multiple single-family dwellings (townhouses)
constructed in accordance with the International Residential Code
for one- and two-family dwellings.
6.6.8 IFC, Chapter 9, Section 903.2.7 is amended to add the
following: Exception: Group R-4 fire areas not more than 4500
gross square feet and not containing more than 16 residents,
provided the building is equipped throughout with an approved
fire alarm system that is interconnected and receives its primary
power from the building wiring and a commercial power
system.
6.6.9 IFC, Chapter 9, Section 903.2.8(2) is deleted and
rewritten as follows: A Group S-1 fire area is located more than
three stories above the lowest level of fire department vehicle
access; or
6.6.10 IFC, Chapter 9, Section 903.2.9 is deleted and
rewritten as follows: Group S-2. An automatic sprinkler system
shall be provided throughout buildings classified as parking
garages in accordance with Section 406.2 or where located beneath
other groups.
6.6.10.1 Exception 1: Parking garages of less than 5,000
square feet (464m2) accessory to Group R-3 occupancies.
6.6.10.2 Exception 2: Open parking garages not located
beneath other groups if one of the following conditions are
met:
6.6.10.2.1 a. Access is provided for fire fighting
operations to within 150 feet (45 720mm) of all portions of the
parking garage as measured from the approved fire department
vehicle access, or
6.6.10.2.2 b. Class I standpipes are installed throughout
the parking garage.
6.6.11 IFC, Chapter 9, Section 903.2.9.1 is deleted and
rewritten as follows: Commercial parking garages. An automatic
sprinkler system shall be provided throughout buildings used for
storage of commercial trucks or buses.
6.6.12 IFC, Chapter 9, Section 903.3.5 is amended by adding
the following at the end of the section: The potable water supply
to automatic fire sprinkler systems and standpipe systems shall
be protected against backflow in accordance with the
International Plumbing Code as amended in the Utah Administrative
Code, R156-56-707, Utah Uniform Building Standard Act
Rules.
6.6.13 IFC, Chapter 9, Section 903.6 is amended to add the
following subsection: 903.6.2 Group A-2 occupancies. An automatic
fire sprinkler system shall be provided throughout existing Group
A-2 occupancies where indoor pyrotechnics are used.
6.6.14 IFC, Chapter 9, Section 904.11 is deleted and
rewritten as follows: Commercial Cooking Systems. The automatic
fire extinguishing system for commercial cooking systems shall be
of a type recognized for protection of commercial cooking
equipment and exhaust systems. Pre-engineered automatic
extinguishing systems shall be tested in accordance with UL300
and listed and labeled for the intended application. The system
shall be installed in accordance with this code, its listing and
the manufacturer's installation instructions. The Exception
in Section 904.11 is not deleted and shall remain as currently
written in the IFC.
6.6.15 IFC, Chapter 9, Sections 904.11.3 and 904.11.3.1 is
deleted and rewritten as follows:
6.6.15.1 Existing automatic fire extinguishing systems used
for commercial cooking that use dry chemical is prohibited and
shall be removed from service.
6.6.15.2 Existing wet chemical fire extinguishing systems
used for commercial cooking that are not UL300 listed and labeled
are prohibited and shall be either removed or upgraded to a UL300
listed and labeled system.
6.6.16 IFC, Chapter 9, Section 904.11.4 is amended to add
the following subsection: 904.11.4.2. Existing automatic fire
sprinkler systems protecting commercial cooking equipment, hood,
and exhaust systems that generate appreciable depth of cooking
oils shall be replaced with a UL300 system that is listed and
labeled for the intended application.
6.6.17 IFC, Chapter 9 Section 904.11.6.4 is amended to add
the following: Automatic fire extinguishing systems located in
occupancies where usage is limited and less than six consecutive
months, may be serviced annually if the annual service is
conducted immediately before the period of usage, and approval is
received from the AHJ.
6.6.18 IFC, Chapter 9, Section 905.11 is deleted.
6.6.19 IFC, Chapter 9, Section 907.2.10.1.4 is created as
follows: Carbon monoxide alarms. Carbon monoxide alarms shall be
installed on each habitable level of a dwelling unit or sleeping
unit in Groups R-2, R-3, R-4, and I-1 equipped with fuel burning
appliances.
6.6.20 IFC, Chapter 9, Section 907.2.10.2 is amended as
follows: On line two, line five, and line one of the Exception,
the word "smoke" is deleted.
6.6.21 IFC, Chapter 9, Section 907.2.10.3 is amended as
follows: On line two and line five, the word "smoke" is
deleted. On line nine after the word "closed", add the
following sentence: "Approved combination smoke and carbon
monoxide detectors shall be permitted."
6.6.22 IFC Chapter 9, Section 907.2.10.4 is amended as
follows: On line five after "NFPA 72" add "and
NFPA 720, as applicable".
6.6.23 IFC, Chapter 9, Section 907.3 is deleted and
rewritten as follows: An approved automatic fire detection system
shall be installed in accordance with the provisions of this code
and NFPA 72. Devices, combinations of devices, appliances and
equipment shall be approved. The automatic fire detectors shall
be smoke detectors, except an approved alternative type of
detector shall be installed in spaces such as boiler rooms where,
during normal operation, products of combustion are present in
sufficient quantity to actuate a smoke detector.
6.6.24 IFC, Chapter 9, Sections 907.3.1, 907.3.1.1,
907.3.1.2, 907.3.1.3, 907.3.1.4, 907.3.1.5, 907.3.1.6, 907.3.1.7,
and 907.3.1.8 are deleted.
6.6.25 IFC, Chapter 9, Section 907.3.2 is amended to add the
following: On line three after the word "occupancies"
add "and detached one- and two-family dwellings and multiple
single-family dwellings (townhouses)".
6.6.26 IFC, Chapter 9, Section 907.3.2.3 is amended to add
the following: On line one after the word "occupancies"
add "and detached one- and two-family dwellings and multiple
single-family dwellings (townhouses)".
6.6.27 IFC, Chapter 9, Section 907.20.5 is amended to add
the following sentences: Increases in nuisance alarms shall
require the fire alarm system to be tested for sensitivity. Fire
alarm systems that continue after sensitivity testing with
unwarranted nuisance alarms shall be replaced as directed by the
AHJ.
6.7 International Fire Code - Means of Egress
6.7.1 IFC, Chapter 10, Section 1008.1.8.3 is amended to add
the following:
6.7.1.1 5. Doors in Group I-1 and I-2 occupancies, where the
clinical needs of the patients require specialized security
measures for their safety, approved access controlled egress may
be installed when all the following are met:
6.7.1.1.1 5.1 The controlled egress doors shall unlock upon
activation of the automatic fire sprinkler system or the
automatic fire detection system.
6.7.1.1.2 5.2 The facility staff can unlock the controlled
egress doors by either sensor or keypad.
6.7.1.1.3 5.3 The controlled egress doors shall unlock upon
loss of power.
6.7.1.1.4 5.4 The secure area or unit with controlled egress
doors shall be located at the level of exit discharge in Type V
construction.
6.7.1.2 6. Doors in Group I-1 and I-2 occupancies, where the
clinical needs of the patients require approved, listed delayed
egress locks, they shall be installed on doors as allowed in IFC,
Section 1008.1.8.6. The secure area or unit with delayed egress
locks shall be located at the level of exit discharge in Type V
construction.
6.7.2 IFC, Chapter 10, Section 1009.3 is amended as follows:
On line five of Exception 4 delete "7.75" and replace
it with "8". On line seven of Exception 4 delete
"10" and replace it with "9".
6.7.3 IFC, Chapter 10, Section 1009.10, is amended to add
the following exception: 6. In occupancies in Group R-3, as
applicable in Section 101.2 and in occupancies in Group U, which
are accessory to an occupancy in Group R-3, as applicable in
Section 101.2, handrails shall be provided on at least one side
of stairways consisting of four or more risers.
6.7.4 IFC, Chapter 10, Section 1012.3 is amended to add the
following: Exception: Non-circular handrails serving an
individual unit in a Group R-1, Group R-2 or Group R-3 occupancy
with a perimeter greater than 6 1/4 inches (160mm)shall provide a
graspable finger recess area on both sides of the profile. The
finger recess shall begin within a distance of 3/4 inch (19mm)
measured vertically from the tallest portion of the profile and
achieve a depth of at least 5/16 inch (8mm) within 7/8 inch
(22mm) below the widest portion of the profile. This required
depth shall continue for at least 3/8 inch (10mm) to a level that
is not less than 1 3/4 inches (45mm) below the tallest portion of
the profile. The minimum width of the handrail above the recess
shall be 1 1/4 inches (32mm) to a maximum of 2 3/4 inches (70mm).
Edges shall have a minimum radius of 0.01 inch (0.25mm).
6.7.5 IFC, Chapter 10, Section 1013.2 is amended to add the
following exception: 3. For occupancies in Group R-3 and within
individual dwelling units in occupancies in Group R-2, as
applicable in Section 101.2, guards shall form a protective
barrier not less than 36 inches (914mm).
6.7.6 IFC, Chapter 10, Section 1015.2.2 is amended to add
the following sentence at the end of the section: Additional
exits or exit access doorways shall be arranged a reasonable
distance apart so that if one becomes blocked, the others will be
available.
6.7.7 IFC, Chapter 10, Section 1028.2 is amended to add the
following: On line six after the word "fire" add the
words "and building".
6.8 International Fire Code - Explosives and Fireworks
6.8.1 IFC, Chapter 33, Section 3301.1.3, Exception 4 is
amended to add the following sentence: The use of fireworks for
display and retail sales is allowed as set forth in UCA 53-7-220
and UCA 11-3-1.
6.8.2 IFC, Chapter 33, Section 3308.12 is a new section as
follows: Display of Class C common state approved explosives
inside of buildings protected throughout with an automatic fire
sprinkler system shall not exceed 25 percent of the area of the
retail sales floor or exceed 600 square feet, whichever is
less.
6.8.3 IFC, Chapter 33, Section 3308.13 is a new section as
follows: Display of Class C common state approved explosives
inside of buildings not protected with an automatic fire
sprinkler system shall not exceed 125 pounds of pyrotechnic
composition. Where the actual weight of the pyrotechnic
composition is not known, 25 percent of the gross weight of the
consumer fireworks, including packaging, shall be permitted to be
used to determine the weight of the pyrotechnic
composition.
6.8.4 IFC, Chapter 33,Section 3308.14 is a new section as
follows: Display of Class C common state approved explosives
inside of buildings shall not exceed a height greater than six
feet above the floor surface.
6.8.5 IFC, Chapter 33, Section 3308.15 is a new section as
follows: Rack storage of Class C common state approved explosives
inside of buildings is prohibited.
6.9 International Fire Code - Flammable and Combustible
Liquids
6.9.1 IFC, Chapter 34, Section 3401.4 is amended to add the
following at the end of the section: The owner of an underground
tank that is out of service for longer than one year, shall
receive a Temporary Closure Notice from the Department of
Environmental Quality and a copy shall be given to the AHJ.
6.9.2 IFC, Chapter 34, Section 3405.5.1 is deleted and
rewritten as follows: Corridor installations. Where wall-mounted
dispensers containing alcohol-based hand rubs are installed in
corridors, they shall be in accordance with all of the following:
1. Level 2 and Level 3 aerosol containers shall not be allowed in
corridors. 2. The maximum capacity of each Class I or II liquids
dispenser shall be 41 ounces and the maximum capacity of each
Level I aerosol dispenser shall be 18 ounces. 3. The maximum
quantity allowed in a corridor within a control group area shall
be 10 gallons of Class I or II liquids or 1135 ounces of Level I
aerosols or a combination of Class I or II liquids and Level I
aerosols not to exceed in total the equivalent of 10 gallons. 4.
Projections into a corridor shall be in accordance with Section
1003.3.3.
6.9.3 IFC, Chapter 34, Section 3406.1 is amended to add the
following special operation: 8. Sites approved by the AHJ.
6.9.4 IFC, Chapter 34, Section 3406.2 is amended to add the
following: On line five after the words "borrow pits"
add the words "and sites approved by the AHJ".
6.10 International Fire Code - Liquefied Petroleum Gas
6.10.1 IFC, Chapter 38, Section 3809.12, is amended as
follows: In Table 3809.12, Doorway or opening to a building with
two or more means of egress, with regard to quantities 720 or
less and 721 - 2,500, the currently stated "5" is
deleted and replaced with "10".
6.10.2 IFC, Chapter 38, Section 3809.14 is amended as
follows: Delete 20 from line three and replace it with 10.
6.11 National Fire Protection Association
6.11.1 NFPA 72, Chapter 2, Section 2.2 is amended to add the
following NFPA standard: NFPA 20, Standard for the Installation
of Stationary Pumps for Fire Protection, 2007 edition.
6.11.2 NFPA 72, Chapter 4, Section 4.3.2.2(2) is deleted and
rewritten as follows: National Institute of Certification in
Engineering Technologies (NICET) fire alarm level II certified
personnel.
6.11.3 NFPA 72, Chapter 4, Section 4.3.3(2) is deleted and
rewritten as follows: National Institute of Certification in
Engineering Technologies (NICET) fire alarm level II certified
personnel.
6.11.4 NFPA 72, Chapter 4, Section 4.4.3.7.2 is amended to
add the following sentence: When approved by the AHJ, the audible
notification appliances may be deactivated during the
investigation mode to prevent unauthorized reentry into the
building.
6.11.5 NFPA 72, Chapter 4, Section 4.4.5 is deleted and
rewritten as follows: Automatic smoke detection shall be provided
at the location of each fire alarm control unit(s), notification
appliance circuit power extenders, and supervising station
transmitting equipment to provide notification of fire at the
location.
6.11.5.1 NFPA 72, Chapter 4, Section 4.4.5, Exception No. 1:
When ambient conditions prohibit installation of automatic smoke
detection, automatic heat detection shall be permitted.
6.11.6 NFPA 72, Chapter 6, Section 6.8.5.9 is amended to add
the following section: 6.8.5.9.3 Automatic fire pumps shall be
supervised in accordance with NFPA 20, Standard for the
Installation of Stationary Pumps for Fire Protection, and the
AHJ.
6.11.7 NFPA 72, Chapter 7, Section 7.4.1.2 is amended as
follows: On line three delete "110dBA" and replace it
with "120dBA".
6.11.8 NFPA 72, Chapter 8, Section 8.3.4.7 is amended as
follows: On line two, after the word "notified" insert
the words "without delay".
6.11.9 NFPA 72, Chapter 10, Section 10.2.2.5.1 is deleted and
rewritten as follows: Service personnel shall be qualified and
experienced in the inspection, testing and maintenance of fire
alarm systems. Qualified personnel shall meet the certification
requirements stated in Utah Administrative Code, R710-11-3, Fire
Alarm System Inspecting and Testing.]
R710-9-[7]6
. Fire Advisory and Code Analysis Committee.
[7]6.1 There is created by the Board a Fire Advisory and
Code Analysis Committee whose duties are to provide direction to
the Board in the matters of fire prevention and building codes.
[7]6.2 The committee shall serve in an advisory position to
the Board, members shall be appointed by the Board, shall serve for
a term of three years, and shall consist of the following
members:
[7]6.2.1 A representative from the State Fire Marshal's
Office.
[7]6.2.2 The Code Committee Chairman of the Fire
Marshal's Association of Utah.
[7]6.2.3 A fire marshal or fire inspector from a local fire
department or fire district.
[7]6.2.4 A representative from the Department of
Health.
[7]6.2.5 The Chief Elevator Inspector from the Utah Labor
Commission.
[7]6.2.6 A representative from the Department of Human
Services.
[7]6.2.7 A representative from Forestry, Fire and State
Lands.
[7]6.3 This committee shall join together with the Uniform
Building Code Commission Fire Protection Advisory Committee to form
the Unified Code Analysis Council.
[7]6.4 The Council shall meet as directed by the Board or
as directed by the Building Codes Commission or as needed to review
fire prevention and building code issues that require definitive
and specific analysis.
[7]6.5 The Council shall select one of it's members to
act in the position of chair and another to act as vice chair. The
chair and vice chair shall serve for one year terms on a calendar
year basis. Elections for chair and vice chair shall occur at the
meeting conducted in the last quarter of the calendar year.
[7]6.6 The chair or vice chair of the council shall report
to the Board or Building Codes Commission recommendations of the
Council with regard to the review of fire and building codes.
R710-9-[8]7. Enforcement of the Rules of the State Fire Marshal.
[8]7.1 Fire and life safety plan reviews of new
construction, additions, and remodels of state owned facilities
shall be conducted by the SFM, or his authorized deputies. State
owned facilities shall be inspected by the SFM, or his authorized
deputies.
[8]7.2 Fire and life safety plan reviews of new
construction, additions, and remodels of public and private schools
shall be completed by the SFM, or his authorized deputies, and the
LFA.
[8]7.3 Fire and life safety plan reviews of new
construction, additions, and remodels of publicly owned buildings,
privately owned colleges and universities, and institutional
occupancies, with the exception of state owned buildings, shall be
completed by the LFA. If not completed by the LFA, the SFM, or his
authorized deputies shall complete the plan review.
[8]7.4 The following listed occupancies shall be inspected
by the LFA. If not completed by the LFA, the SFM, or his authorized
deputies shall inspect.
[8]7.4.1 Publicly owned buildings other than state owned
buildings as referenced in 9.1 of this rule.
[8]7.4.2 Public and private schools.
[8]7.4.3 Privately owned colleges and universities.
[8]7.4.4 Institutional occupancies as defined in Section
9-2 of this rule.
[8]7.4.5 Places of assembly as defined in Section 9-2 of
this rule.
[8]7.5 The Board shall require prior to approval of a grant
the following:
[8]7.5.1 That the applying fire agency be actively
participating in the statewide fire statistics reporting
program.
[8]7.5.2 The Board shall also require that the applying
fire agency be actively working towards structural or wildland
firefighter certification through the Utah Fire Service
Certification System.
R710-9-[9]8. Fire Prevention Board Budget and Amendment
Sub-Committees.
[9]8.1 There is created two Fire Prevention Board
Sub-Committees known as the Budget Subcommittee and the Amendment
Subcommittee. The subcommittees membership shall be appointed from
members of the Board.
[9]8.2 Membership on the Sub-Committee shall be by
appointment of the Board Chair or as volunteered by Board members.
Membership on the Sub-Committee shall be limited to four Board
members.
[9]8.3 The Sub-Committee shall meet as necessary and shall
vote and appoint a chair to represent the Sub-Committee at
regularly scheduled Board meetings.
R710-9-[10]9. Repeal of Conflicting Board Actions.
All former Board actions, or parts thereof, conflicting or inconsistent with the provisions of this Board action or of the codes hereby adopted, are hereby repealed.
R710-9-[11]10. Validity.
The Utah Fire Prevention Board hereby declares that should any section, paragraph, sentence, or word of this Board action, or of the codes hereby adopted, be declared invalid, it is the intent of the Utah Fire Prevention Board that it would have passed all other portions of this action, independent of the elimination of any portion as may be declared invalid.
R710-9-[12]11. Adjudicative Proceedings.
[12]11.1 All adjudicative proceedings performed by the
agency shall proceed informally as set forth herein and as
authorized by UCA, Sections 63G-4-202 and 63G-4-203.
[12]11.2 If a city, county, or fire protection district
refuses to establish a method of appeal regarding a portion of the
IFC, the appealing party may petition the Board to act as the board
of appeals.
[12]11.3 A person may request a hearing on a decision made
by the SFM, his authorized deputies, or the LFA, by filing an
appeal to the Board within 20 days after receiving final
decision.
[12]11.4 All adjudicative proceedings, other than criminal
prosecution, taken by the SFM, his authorized deputies, or the LFA,
to enforce the Utah Fire Prevention and Safety Act and these rules,
shall commence in accordance with UCA, Section 63G-4-201.
[12]11.5 The Board shall act as the hearing authority, and
shall convene as an appeals board after timely notice to all
parties involved.
[12]11.6 The Board shall direct the SFM to issue a signed
order to the parties involved giving the decision of the Board
within a reasonable time of the hearing pursuant to UCA, Section
63G-4-203.
[12]11.7 Reconsideration of the Board's decision may be
requested in writing within 20 days of the date of the decision
pursuant to UCA, Section 63G-4-302.
[12]11.8 Judicial review of all final Board actions
resulting from informal adjudicative proceedings is available
pursuant to UCA, Section 63G-4-402.
KEY: fire prevention, law
Date of Enactment or Last Substantive Amendment: [May 27, 2009]July 1, 2010
Notice of Continuation: June 8, 2007
Authorizing, and Implemented or Interpreted Law: 53-7-204
Additional Information
The Portable Document Format (PDF) version of the Bulletin is the official version. The PDF version of this issue is available at https://rules.utah.gov/publicat/bull-pdf/2010/b20100515.pdf. The HTML edition of the Bulletin is a convenience copy. Any discrepancy between the PDF version and HTML version is resolved in favor of the PDF version.
Text to be deleted is struck through and surrounded by brackets (e.g., [example]). Text to be added is underlined (e.g., example). Older browsers may not depict some or any of these attributes on the screen or when the document is printed.
For questions regarding the content or application of this rule, please contact Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at [email protected].